Title |
Reliability Assessment Considering PLOC and Unified Evaluation via Analytic Network Process |
Abstract |
This paper describes the unified reliability evaluation with partial loss of continuity for Inchon international airport distribution system which is complex and difficult system to implement. To evaluate reliability considering line limitation and voltage drop of the system, PLOC technique which is based on deterministic evaluation technique and failure mode & effective analysis method is employed. And reliability indices calculation method is used. Finally, to evaluate the system performance and to improve the reliability of the system, Analytic network process method is employed. As a result, calculating accurate reliability, finding weak points, and expansion scheduling of the system is possible. |