Title |
The development of LVI tester for application of transformers winding deformation diagnosis |
Authors |
Kook-Hee Cho ; Kwang-Hwa Kim |
Abstract |
The assessment of the condition of a transformer winding which is suspected of having suffered short circuit damage can be difficult. Conventional test such as winding resistance, magnetic current or insulation resistance will only detect damage if a permanent electrical fault exists. Visual inspection of windings necessitates the removal of oil and in many cases only a very small proportion of the winding can be seen. We describe the characteristic of LVI test system and methods to detect the deformation of windings in the power transformers. As the front rise time of recurrent-surge generator pulse less than 1000 ns and the peak value of pulse is about 500 V, we have the good results of detecting winding deformation in the LVI test of transformers. |