Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title A Study on the Measurements, Moldeling, and Passive Filter Application of Neutral Harmonic Currents by Field Tests
Authors Kyung-Chul Kim ; Yun-Mo Kang ; Il-Moo Lee
Page pp.103-111
ISSN 1225-1135
Abstract With the proliferation of nonlinear loads such as personal computer in an educational building, high neutral harmonic currents have been observed. High neutral currents in three-phase four wire distribution power systems can cause lots of harmonic problems such as overloaded neutral conductors and malfunction of protective equipment. On-site measurements of harmonic currents and voltages were made and the corresponding equivalent circuits was developed. The circuit model under study was simulated numerically and graphically through the use of the software MATLAB. Simulation results verifying the effects of a single-tuned passive filter for the neutral harmonic current reduction are presented.