Title |
A Study on the Economical Design of Airport Low-Voltage Feeder which is considering the Temperature Character |
Authors |
Hong-Kyu Choi ; Kyeh-Sool Cho ; Young-Joo Song |
Abstract |
The size of low voltage level conductor cables can be installed with a long length just like a aviation field shall be determined for considering the ampacity of cable and the drop of voltage for the power system. Therefore, The size of the conductor cables may be larger one for considering the tolerable voltage drop comparatively, although the allowable ampacity of the conductor cables may have a margin in comparison with the rated full load current. In this case, the conductor cables" allowable ampacity will be very larger than the rated full load current and the generated heat of the conductor will be relatively downed. The conductor cables" applied on the general formula for the calculating the voltage drop in determinating the size of low voltage level conductor cables, and the resistance is larger than the resistance conducted with the actual temperature of the conductor cables. This paper was studied for the purpose of the conductor resistance corrected with the actual temperature rise of the conductor and address the economic design formula so that this studies shall minimize the errors which can be occurred in comparison with the general formula and which can be applied in design work for determining the size of low voltage level conductor cables. |