Title |
Characteristics of Radiated Electromagnetic Wave and Partial Discharge in Power XLPE Cable |
Authors |
Hyun-Chul Lee ; Kwang-Seo Park ; Dae-Hee Yoon ; Sang-Hoon Lee ; Jong-Hwan Kim ; Chung-Nyun Kim ; Ki-Chai Kim ; Kwang-Sik Lee |
Keywords |
XLPE power cable ; Radiated electromagnetic waves ; partial discharge ; UHF method |
Abstract |
This paper simulated partial discharge caused by 22.9[㎸] power cable using XLPE(Peroxide Crosslinkable Polyethylene) insulation having the outside damage . As one of the insulation diagnostic method a radiated electromagnetic waves were measured by an UHF method using a BiconiLog antenna(EMCO-3142) and a spectrum analyzer used to measure EMI, EMC. From results of this study, It was confirmed that discharge progress were possible to be estimated by the proposed method. |