Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Development of the New Harmonic Eliminating Device Using Zig-Zag Connection and Open-Delta Mode
Authors Sung-Ho Lee ; Gi-Sung Kim ; Sang-Bong Yoo
Page pp.169-174
ISSN 1225-1135
Keywords New Harmonic Eliminating Device(HANOS) ; Zig-Zag Connection ; Open-Delta Mode
Abstract The conventional harmonic filters to reduce zero harmonic current from neutral reactors and Zig-Zag connection, have several disadvantages of the decreased reduction rate of harmonics under a light load, because they have the load factor-dependent reduction rate of harmonics, and the risk of potential breaking in the neutral line by heated neutral reactor. Based Zig-Zag connection and Open-Delta mode, this new harmonic eliminating device (HANOS) adopts the combination of Zig-Zag connection and Open-Delta mode-the latter is additionally applied to the transformer’s core block for connection to the neutral line. The results of this study demonstrated that the new device could eliminate safely zero harmonic current running in the neutral line without heating.