Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title A Study on DC Charging Algorithm of the Line?Interactive UPS with Dual Converter Structure
Authors Woo-Cheol Lee ; Dong-Sang Yoo
Page pp.27-34
ISSN 1225-1135
Keywords Line-Interactive UPS ; dual converter structure ; DC charging
Abstract This paper presents a three?phase Line-Interactive uninterruptible power supply(UPS) system with dual converter structure. The three?phase UPS system consists of two active power compensator topologies. One is a series active compensator, which works as a voltage source in phase with the source voltage to have the sinusoidal source current and high power factor under the deviation and distortion of the source voltage. The other is a parallel active compensator, which works as a conventional sinusoidal voltage source in phase with the source voltage, providing to the load a regulated and sinusoidal voltage with low total harmonic distortion(THD). This paper presents in the series and parallel active compensator charging method depending on the amplitude of the source voltage. The conventional Line-Interactive UPS system is responsible for the DC charging and output voltage regulation at the same time, but UPS system with dual converter structure, a series active compensator can also charge the DC link. Therefore, the charging algorithm using the series and parallel compensator needs to be researched. Therefore, by making the DC link voltage stable, it can contribute the stability of series and parallel compensator. The simulation and experimental result are depicted in this paper to show the effect of the proposed algorithm.