Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title An Improved Method for Mesh Grounding System Using Spaced Arrangement of Grounding Conductor
Authors Hong-Kyu Choi ; Young-Joo Song
Page pp.57-65
ISSN 1225-1135
Keywords Mesh grounding system ; Unequally spaced grounding grid ; Poly-nominal function form
Abstract No matter how well the equally spaced grounding grid is designed, there are questions keep rising, such as leakage of current from corner conductor, high voltage of touch voltage in corners of grid than in center, and high material cost for grounding grid. The best-fitted design for unequally spaced grounding grid is a part that must be considered. Explain advantages of unequally spaced grounding grid and lead formula by dividing the number of grid division, j, into 20, instead of 7. Then, present Dij, which is optimum rate for unequally spaced grounding grid and verify safety and economy of the unequally spaced grounding grid by computer simulation with a poly-nominal function form.