Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title A Study on the Transformer Capability Containing Harmonic Load Currents
Authors Kyung-Chul Kim ; Sang-Young Park ; Il-Moo Lee ; Ju-Hong Lee ; Seong-Eun Jin
Page pp.23-29
ISSN 1225-1135
Keywords Harmonic currents ; Transformer derating ; Transformer capability ; Capacitor bank ; Harmonic filter
Abstract The increasing use of nonlinear loads has resulted in an increase in the harmonic content of the load current for power transformers. Transformers subject to harmonic currents have higher losses and need to be derated. This paper presents a simple method for determining the capability of transformers to supply harmonic load currents and shows that the application of capacitor banks with a series connected reactor and harmonic filters will greatly increase the capability of transformers. The EDSA program was used as a simulation tool for the case study.