Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title The Characteristics Analysis of New Dc 48[Ⅴ] Telecommunication Power System using Forward Type three Phase Rectifier
Authors Ki-Young Suh
Page pp.34-40
ISSN 1225-1135
Keywords Telecommunication ; IEC61000-3-2 ; High-Frequency isolated
Abstract This paper proposed power system for new DC 48[Ⅴ] telecommunication using forward three-phase PWM rectifier power factor and efficiency for improvement of ripple voltage. Proposed power system for DC 48[Ⅴ] telecommunication that consists of power conversion devices including switch, inductor and condenser were made between each line, in power inverter device of each switch control turn-on in period of continuity time control to get power factor “1” of sine wave current and on-off of switch lessens peak current that was happened and got conversion efficiency 92.1[%] composing in PWM rectifier of forward form instead of general PWM rectifier. Also, harmonic input regulation value(IEC61000-3-2 Class-As) satisfy input current and reduce ripple factor of output voltage in state that distortion of three-phase supply is overlapped each other.