Title |
Evaluation of Potential Interferences between Grounding Electrodes using an Electrolytic Tank |
Authors |
Bok-Hee Lee ; Su-Bong Lee ; Tae-Hyung Lee ; Hyeong-Joon KIl |
Keywords |
Potential interferences coefficients ; Potential rise ; CDEGS ; Hemispherical grounding simulation system ; Ground rod ; Ground grid |
Abstract |
This paper deals with the potential interferences between grounding electrodes in various grounding electrodes. The ground potential rise and potential interference coefficients were measured by using and electrolytic tank and calculated by CDEGS program as functions of the configuration and size of grounding electrodes and the distance between grounding electrodes. The ground potential rise and potential interference coefficient strongly depend on the distance between grounding electrodes, the shape and size of grounding electrodes. The potential rise interferences between grounding grid and grounding grid is lower than those between grounding grid and ground rod. |