Abstract This research is contents about output characteristic of optic current sensor that use faraday effect. optic current sensor used in an experiment is consisted of three parts.① Source of light used laser diode of 1310 [㎚].② Sensor section manufactured circularly according to gas insulated switchgear. And 9/125[ ㎛ ] standard single mode optical fiber for communication was installed winding 20 [turn] on sensor section core surroundings of diameter 31 [㎝]. ③ Electrical signal of PD(Photo detector) is collected using NI company"s 16bit DAQ board via terminal block. Collected data analyzed by different three signal processing methods. NI company"s LabviewTM was used to signal processing software. As a result, In signal processing of optic current sensor, we could know that noise greatly more influences the error generation than fluctuation of light intensity. also, 1 class CT(current transformer) manufacture that have error rate less than 1[%] was available by removing these