Title Analysis on the Effect of Filter to Mitigate Transient Overvoltage on the High Voltage Induction Motor Fed by Multi Level Inverter using EMTP
Authors Young-Mok Kwon ; Jae-Chul Kim
Page pp.82-93
ISSN 1225-1135
Keywords ASD ; Cable ; EMTP ; High-voltage Induction motor ; PWM ; Switching surge
Abstract In this paper, filters are designed to reduce transients overvoltage in inverter fed high-voltage large-capacity induction motor drive system. Design issues for a LCR filter at the inverter output terminals to reduce the dv/dt of the inverter output pulse and a RC filter at the induction motor input terminals to match the characteristic impedance between cable and induction motor are examined in detail. These filters are modeled to be suitable to high-voltage large-capacity induction motor. The performance of the filter is evaluated through simulation using EMTP (ElectroMagnetic Transients Program). We presented filters that used high voltage large-capacity induction Motor on the basis of this. Effect of the filter is analyzed for variation of the cable length. Characteristics of filters are analyzed to reduce harmonic in voltage waveform of induction motor input terminal. The switching surge voltage became the major cause to occur the insulation failure by serious voltage stress in the stator winding of i duction motor. Filter for to mitigate transients overvoltage presents a required component in drive system of high-voltage large-capacity induction motor. Also, proposed filters are proved through simulation using EMTP.