Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Improvement of Simultaneous Quench Characteristic of Flux-lock Type Superconducting Fault Current Limiters Through Its Series Connection
Authors Sung-Hun Lim
Page pp.102-106
ISSN 1225-1135
Keywords Flux-Lock Type Superconducting Fault Current Limiter (Sfd) ; Simultaneous Quench
Abstract To apply the flux-lock type superconducting fault current limiter (SFCL) into power system, its current and voltage ratings are required to increase. Especially, in case of series connection of SFCLs, the countermeasure for simultaneous quenches must be considered. The structure, which each flux-lock type SFCL unit was wound in series on the same iron core, can induce the simultaneous quench of superconducting elements. Through the fault current limiting experiment for the suggested structure, it was confirmed that the even voltage burden among the superconducting elements comprising SFCLs could be made.