Keywords Transformer ; Dissolved Gas Analysis ; Diagnosis
Abstract This paper presents new criteria for DGA (Dissolved Gases Analysis) using CDF (Cumulative Distribution Function) obtained from the data from the diagnosis of transformers operated in KEPCO over a period of 16 years. Because of differences in operating environments, construction type, oil volume, and other factors, the interpretative criteria of DGA at KEPCO differs from other standards such as IEC-60599, or Rogers and Doemenburg. To suggest the most appropriate criteria, the DGA data from transformers under normal conditions as well as from developing fault transformers were collected. Using these data, this study suggests the limitative gas level of transformers under normal operating conditions and verifies the suitability of the criteria. Because the application of this new criterion to transformers at KEPCO increases the detectable ratio of incipient faults and reduces unnecessary follow-up sampling and analysis, the new criteria yields a more reliable prediction of transformer condition.