Title |
Model Parameter Determination of Industrial Co-generator Model Parameters through Filed Measurement |
Keywords |
DG ; Co-Generator ; Model Parameter ; On-Site Characteristic Testing ; Validation Of Model Parameters |
Abstract |
This paper presents a method for the derivation of model parameters of a co-generation system using data measured through on-site generator characteristic testing and validates its model parameters. Dynamic models such as generator, excitation system, and turbine/govemor are mainly dealt in this paper. For the purpose of validation of derived model parameters, the measured results are compared with simulation results. The comparisons between measured results and simulation results show good match. |