Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Influence of Defects on Electrical Characteristics of Distributing Cable Termination
Authors Sang-Hyun Kim ; Jae-Hyeong Choi ; Jin-Wook Choi ; Young-Seok Kim ; Sun-Gu Kim ; Seung-Myeong Baek
Page pp.190-195
ISSN 1225-1135
Keywords Distributing Cable Termination ; Electrical Accident ; Breakdown ; Withstand Test
Abstract This paper introduces experimental investigates of an electrical accident of the distributing cable termination with simulated a shoddy construction. We prepared two termination kites, one is built-in type, the other is heat contraction type. Also, we manufactured cable termination that have simulated defect by badness construction and investigated their insulation characteristics such as ac (35[㎸], 1[min]) and impulse (95[㎸], 1.2×50[㎲]) withstand test. The influence of defects such as thickness decrease, the gap between stress-con of housing and semiconductor and heating time on insulating properties of the termination have been studied. The thickness decrease of an insulator decreases ac breakdown strength suddenly and the breakdown traces of the insulator that is damaged by knife displayed elliptic shape. The gap of between stress-con and semiconductor deteriorates dielectric strength of insulator seriously. In heat contraction type, the ac breakdown voltage became low when the heating time is short.