Title Analyses of Hazard Voltages According to the Buried Depth of Small-sized Model Grounding Electrode
Authors Young-Hwan Baek ; Bok-Hee Lee
Page pp.56-61
ISSN 1225-1135
Keywords Ground rod ; Touch voltage ; Step voltage ; Ground surface potential rise ; Scale model test
Abstract This paper presents the ground surface potential profiles and hazard voltages around the metallic structure connected to a small-sized model ground electrode. Because it is very difficult to draw valid conclusions concerning a general grounding problem from actual field data, scale model tests can be used to determine the touch and stop voltages and surface potential profiles around ground electrode. In this work, a hemispherical vessel with a diameter of 1,100[mm] was employed to simulate uniform soil. As a result, the ground surface potential around the ground electrode was significantly raised. In particular the ground surface potential at the just upper point of ground rod was higher than other points. When the buried depth of ground rod is increased, the ground surface potential and step voltage were lowered but the touch voltage was elevated.