Title |
An Investigation into the Actual Condition of Electrical Equipments Installation for the Inspection Method Development Based on IEC 60364 |
Authors |
Jin-Soo Jung ; Woon-Ki Han ; Han-Sang Lee |
Keywords |
IEC 60364 ; TN-C-S ; TT ; Protective Conductor ; Loop Impedance |
Abstract |
In this paper an Investigation into the actual condition of electrical equipments installation for the inspection method development based on IEC 60364. The analysis objects are the difference between electrical equipments installation in korea & electrical equipments installation based on the IEC 60364. The measurement elements are loop impedance, operating characteristic of circuit breaker and protective conductor continuance. As a result, the korea electrical equipments installation was almost same the TT system but some different of protective conductor continuance. Electrical equipments installed TN-C-S has noting problem about installation but manager dose not understand about IEC 60364. |