Title |
Flashover Characteristics of Vertical-type Model Power Line in the Presence of Combustion Flame |
Keywords |
Flashover Characteristics ; Model Power Line ; Combustion Flame |
Abstract |
A forest fire in the area of power line installations may be caused by flashover disturbances in power systems. In this study, experiments were conducted so as to investigate the reduction in dielectric strength caused by combustion flame, and flashover characteristics in the simulated condition of vertical-type model power lines were examined by making shorter and longer the horizontal distance(s) between combustion flame and high-voltage conductors under the application of 60[㎐] a.c. and d.c. high-voltages. As the results of the experimental investigation, it is demonstrated that flame can reduce flashover voltages of the model air-gap in shorter range of the horizontal distance(s). Relative air density is considered in order to analyze the reduction causes of the flashover voltages, and it can be seen that the relative air density has a great influence on the flashover characteristics under the presence of combustion flame. |