Title Horizontal Displacement Analysis of Electric Pole from Full Scale Pull-Out Test in Softground
Authors Tae-Bong Ahn
Page pp.115-126
ISSN 1225-1135
Keywords Electric Pole ; Anchor Block ; Pull-Out Test ; Displacement
Abstract Many electric poles in the softground have been collapsed due to external load such as typhoon wind load. In this study, the location, numbers and depths of acnchor blocks as well as depth of poles were varied to find horizontal displacement of poles through pull-out tests. The 10 types of tests were performed, and lateral displacements showed differences depending on location, numbers and depth of poles. The bending is generated in the upper part at the initial load, but it moved to central part as load increased. The maximum horizontal displacement decreased to 1/1.6 at -0.5[m] depth of anchor block and 1.3[m] additional laying depth of poles into ground. Two anchor blocks of poles are better than one acnchor block system, but one anchor block system is recommended because difference of displacement is not too large, and constructibilty is bad due to increase of excavation for anchor blocks.