Title A Study on the Integrated Monitoring of a Leakage Current of the Grounding Wire of Neutral Point of the Low Voltage Side of Transformer
Authors Soon-Seuk Hong ; Joon-Yeal Park ; Jung-Eun Lee ; Kyung-Han Choi
DOI http://dx.doi.org/10.5207/JIEIE.2010.24.5.106
Page pp.106-113
ISSN 1225-1135
Keywords Leakage Current ; A Grounding Wire Of A Neutral Point ; Integrated Monitoring
Abstract If leakage current is neglected, it can become a cause for disasters such as electric shock and fire, therefore a continuous monitoring is necessary. However in most cases, because management of substations is performed by unmanned systems, or walk-around inspections, continuous monitor is difficult. So when an accident occurs and the cause is not immediately resolved causing the emergency generator’s OCGR getting activated by the leakage current that in turn cut off the ACB, the emergency generator may stop working. To prevent such a problem, a real-time integrated monitoring system for monitoring the leakage current returning to the grounding wire of neutral point of the low voltage side of transformer is proposed. Therefore in this paper, the effects of flow of leakage current, which is caused by insulation degradation phenomena or insulation destroy phenomena, were identified by simulation. And through cases studies; the excellence of integrated monitoring system was verified.