Title |
A Study on the Emergency and Recovery AC/DC Combination Lamps in the Electric Substations |
Authors |
Joon-Yeal Park ; Youn-Ki An ; Jong-Soo Kim ; Hye-Young Shin |
DOI |
http://dx.doi.org/10.5207/JIEIE.2010.24.6.027 |
Keywords |
Emergency and Recovery Lamp ; AC/DC Lamp ; The Electric Substations |
Abstract |
This study is for the improvement in the equipment environment of the emergency and recovery lamps in electric substations. To solve problem about the weak illuminance of existing emergency lamps, the AC/DC combination lamps and switches are reviewed. And the improved illuminance standards that are divided each room"s purpose are suggested. It is based on a nuclear power plant"s Illuminance Standards and a safety lamp"s Illuminance Standards of Illuminance Standards Korean Industrial Standards - KS A 3011 -, not just 5~10[%] in according with normal lamp"s illuminance. Lastly, The experiments are conducted to prove the suggested contents on this study. Consequently, a battery capacity is not increased, but illuminance of emergency and recovery lamps can be increased. |