Abstract This paper describes the characteristic of tracking progress happened at the end of the polyvinyl chloride insulated cabtyre oval cord(VCTFK) that is widely used for distribution cord. Tracking is occurred owing to the drop of electrolyte at the end of the VCTFK. The tracking progress and its characteristic happened at the end of the VCTFK are as follow; Carbonization and electrical erosion are happened at the end of the VCTFK. Electrical erosion is begun at the insulation layer near conductors. After that, it is also happened at the sheath layer. Accumulation of carbonized insulation and sheath materials at the end of the VCTFK is begun after progress of electrical erosion. When the accumulation is progressed arc discharge is appeared and finally it goes to tracking breakdown.