Title |
Comparison of Operating Characteristics for DFIG and FSIG wind Turbine Systems with Respect to Variable Interconnecting Line Conditions |
Authors |
Kyoung-Soo Ro ; Tae-Ho Kim |
DOI |
http://dx.doi.org/10.5207/JIEIE.2010.24.9.008 |
Keywords |
Wind Turbine System ; DFIG ; FSIG ; Fault Current ; MATLAB/Simulink |
Abstract |
This paper analyzes the steady-state output characteristics of variable-speed wind turbine systems using doubly-fed induction generators(DFIG) compared with fixed-speed induction generator(FSIG) wind turbine systems. It also presents simulations of a grid-connected wind turbine generation system for dynamics analysis on MATLAB/Simulink and compares the responses between DFIG and FSIG wind turbine systems with respect to wind speed variation, impedance changes and X/R ratio changes of interconnecting circuits. Simulation results show the variation of generator"s active output, terminal voltage and fault currents at the interconnecting point. Case studies demonstrate that DFIG wind turbine systems illustrate better performance to 3-phase fault than FSIG"s. |