Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Stress Analysis Acting on Electric Pole using Strain Gauge from Full Scale Pull-Out Test
Authors Tae-Bong Ahn
DOI http://dx.doi.org/10.5207/JIEIE.2010.24.9.049
Page pp.49-55
ISSN 1225-1135
Keywords Electric Pole ; Anchor Block ; Pull-Out Test ; Stress
Abstract Many electric poles in the softground have been collapsed due to external load. In this study, 10 types of tests were performed with variation of location, numbers and depths of anchor blocks as well as depth of poles to find stresses acting on concrete electric poles. The stresses of concrete poles are relaxed at 600~700[㎏] of tensile load, and stresses are concentrated at top of pole, and spread to lower part of pole. In the concrete pole collapse test, tensile load at failure was approximately 1,400[㎏], which is twice of design load. As passive zone in the soil increases, the stresses acting on concrete pole are concentrated at lower part of pole based on moment arm earth pressure distribution.