Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title The Effect by Grounding Resistance of the ground Fault in the 22.9[㎸] Multi-ground Distribution System
Authors Kum-Young Jung ; Sun-Kyu Choi ; Keon-Bo Shim ; Kyung-Chul Kim
DOI http://dx.doi.org/10.5207/JIEIE.2010.24.10.085
Page pp.85-89
ISSN 1225-1135
Keywords Power Distribution System ; Multi-Grounded Neutral Grounding ; Ground Fault Current ; Grounding Resistance
Abstract During a ground fault the maximum fault current and neutral to ground voltage will appear at the pole nearest to the fault. Distribution lines are consisted of three phase conductors, an overhead ground wire and a multi-grounded neutral line. In this paper phase to neutral faults were staged at the specified concrete pole along the distribution line and measured the ground fault current distribution in the ground fault current, three poles nearest to the fault point, overhead ground wire and neutral line. A effect by grounding resistance of poles of ground fault current in the 22.9[㎸] multi-ground distribution system. by field tests.