Title |
A Study on the Life Time of RCD in Coastal Area |
Authors |
Chong-Min Kim ; Myeong-Il Choi ; Kil-Mok Shong ; Jung-Youl Seo ; Jin-Yong Shin ; Chang-Hwan Kim |
DOI |
http://dx.doi.org/10.5207/JIEIE.2011.25.1.085 |
Keywords |
RCD ; MTTF ; Accelerated Life Test ; B10 Life Time |
Abstract |
The role of RCDs(Residual Current Protective Device) that are installed before the load is very important for preventing electric shock and electrical fire. However, although fault rate of RCD is increasing due to deterioration and long period usage, the RCD is permanently used without a checking of performance evaluation and it causes the electrical accident. In this paper, the amount of airborne chloride is researched in domestic costal area and the accelerated life test is conducted using a salt water spray tester in order to decide the life time of RCD. As a result of an accelerated life test, the MTTF(Mean Time To Failure) of RCD is 110.81 hours and B10 life time of RCD is 45.81 hours for the all samples. when an accelerated life test result is applied to within 2 km costal area, the life time of RCD is predicted about 5 years. |