Abstract |
This paper deals with the electromagnetic clutch which stop the generator at emergency by using the engine power of generator. The electromagnetic field was analyzed using Flux-2d program with different conditions : voltage, air gap, coil locations. As a result, the maximum magnetic flux density of electromagnetic clutch occurred between the coil and wheel : 0.27[T], 0.41[T] at 12[V], 24[V]. The maximum flux density was at the center location of the coil. |