Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Experimental Study of The Floating-Phenomenon on Neutral Ungrounded UPS System
Authors Hae-Sup Shim
DOI http://dx.doi.org/10.5207/JIEIE.2011.25.5.067
Page pp.67-72
ISSN 1225-1135
Keywords Neutral Floating-Phenomenon ; Phantom Voltage ; Transient Overvoltage
Abstract In this study we investigate the background of UPS output transformer(△-Y) operation on neutral ungrounded system, and perform field experiment of neutral floating-phenomenon for the inter-locked securing of electric facilities and improvement of neutral floating-phenomenon. Experiment results show that a floating-phenomenon occurs when four-pole input-breaker trip and the neutral to earth voltage occurring concurrently is identified as phantom voltage. And the measures for the transient overvoltage that can occur in floating-state also are investigated. As a result, the risk elements of neutral ungrounded method as well as neutral floating-phenomenon are removed by installation of separate solidly-grounded transformer and switching four-pole input-breaker to three-pole input breaker.