Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Analysis of Fault Point’s Distant Effect in Power Distribution System with Superconducting Fault Current Limiter
Authors Myong-Hon Kim ; Jn-Seok Kim ; Sung-Hun Lim ; Jae-Chul Kim
DOI http://dx.doi.org/10.5207/JIEIE.2011.25.9.044
Page pp.44-49
ISSN 1225-1135
Keywords Superconducting Fault Current Limiter(SFCL) ; Power Distribution System ; Distance of Fault Point
Abstract Due to increase of fault current, various superconducting fault current limiter (SFCL) are researched. We studied a power distribution system with SFCL. Along the way, we knew characteristics of fault current according to a distance from substation to fault point. Fault current is reduced by distance’s increase from substation. Also, SFCL’s effects are decreased by distance too. Therefore, we analyzed the fault current by a distance from substation to fault point when a SFCL was applied into a power distribution system. We simulated using a PSCAD/EMTDC.