Title |
Experimental Verification on the Use of Steelwork as a Down-Conductor in Lightning Protection System |
DOI |
http://dx.doi.org/10.5207/JIEIE.2011.25.9.094 |
Keywords |
Steelwork ; Reinforced Concrete ; Lightning Protection System ; Down-Conductor System |
Abstract |
This paper verified the characteristics of electrical continuity and mechanical strength of steelwork required to use it as a down-conductor in lightning protection system. It was proven that the steelwork in reinforced concrete apartment has an excellent electrical continuity with low resistance(less than 0.2[Ω].). But it was confirmed that a poor connection between two reinforcement bars can easily cause serious damages of the concrete even with the impulsive current of 50[㎄], 10/350[㎲]. These results of experiments mean that the additional measures are necessary in using the steelwork as the down-conductor of the lightning protection system. |