Site Evaluation and Application of the On-line and Off-line Test for the 13[kV] Class Hydropower Generator Stator Windings |
Authors |
Jeong-Ho Chang ; Dong-Keun Lee ; Heyng-Ho Lee |
DOI |
http://dx.doi.org/10.5207/JIEIE.2011.25.11.073 |
Keywords |
Hydro Generator ; Stator Winding ; Partial Discharge ; On-line PD ; Off-line Diagnosis |
Abstract |
The solid insulation system of stator windings in high voltage rotational machines is usually aging in accordance with long time operation. The partial discharge test have been known to check whether insulation deterioration exist or not, and the PD test can effectively diagnose a solid insulation condition regardless of during operation(on-line) or not(off-line).The on-line PD measurement have proven to be a successful technique in monitoring stator insulation condition nowadays. This paper describes the characteristics of comparing the on-line PD measurement data using PDMS-HG(Partial Discharge Monitoring System for Hydro-electric Generator) installed in field with the off-line diagnosis measurement data(insulation resistance, winding resistance, PI, Δtanδ and PD) on hydro generator(13[kV]) stator windings. These results make good use of managing rotational machines through evaluating the solid insulation condition of stator windings. |