Title Mesh Grounding Design Based on the Study of Dangerous Voltage on Limited Sites
Authors Seok-Geum Son ; Jae-Chul Kim
DOI http://dx.doi.org/10.5207/JIEIE.2011.25.11.091
Page pp.91-97
ISSN 1225-1135
Keywords Dangerous Voltage ; Mesh Grounding ; Grounding Design
Abstract In Korea, characterized in most cases by limited area or high earth resistivity, it is likely to design narrow distances between grounding conductors, with a view to keeping ground resistance and touch voltage below the safety margin values. A new grounding method is suggested, making use of double meshes, to lower touch voltage in a confined area, since it is difficult to lay the plugs under the ground with narrow gaps between them on a limited site. For the presentation of a new model, the suggested grounding system has been analyzed and studied in ground resistance, touch voltage and step voltage, using IEEE Std. 80 calculations and computer simulations.