Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title An Analysis of Potential Interference Effects in the Vicinity of Ground Rod Depending on Frequency of Ground Currents
Authors Bok-Hee Lee ; Yong-Seung Cho ; Jong-Hyuk Choi ; Soon-Man Yang
DOI http://dx.doi.org/10.5207/JIEIE.2011.25.12.088
Page pp.88-93
ISSN 1225-1135
Keywords Potential Interference ; Ground Surface Potential Rise ; Grounding Impedance ; Vertical Ground Rod
Abstract When the ground current is injected into the adjacent ground electrode, the potential interference is caused between ground electrodes. the ground potential interferences have been largely studied with power frequency fault currents. Many attempts to find the frequency-dependent grounding impedance report that the high frequency grounding impedance is very different with the ground resistance. This paper presents experimental data on the frequency-dependent potential interference effects in the vicinity of ground rod. The ground potential rises around the test ground rod of 4 or 6[m] were measured and discussed. As a result, the ground potential rises and potential interference factor are decreased with decreasing the grounding impedance. It was found that the lowering of grounding impedance is critical to reduce the ground potential interference effects.