Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Characteristics Analysis of Reactor Considering Magnetization Saturation
Authors Jong-Gyeum Kim ; Young-Jeen Park
DOI http://dx.doi.org/10.5207/JIEIE.2012.26.2.092
Page pp.92-98
ISSN 1225-1135
Keywords Magnetization Curve ; Nonlinear Load ; Reactor ; Capacitor ; Harmonics
Abstract As the increasing of non-linear load, filter is coming to be high gradually in order to reduce the harmonic which occurs from the power conversion. The maintenance of passive filter is easier than active filter and it has been widely used in the industrial site. This passive filter is connected with condenser and reactor by series and parallel and it is installed at the front of nonlinear load. The breakdown of passive filter occurs frequently at the reactor side rather than capacitor. So the breakdown cause close examination is necessary. In this paper, we analyzed that the electric stress of reactor which is considered magnetization saturation at the passive filter. we confirm that the reduction of harmonics and the electric stress of reactor is influenced by the linear and non-linear element of reactor.