Title |
A Study on the Harmonics and Flicker Measurements and Analysis of the Grid Connected Photovoltaic Power System |
Authors |
Kyung-Chul Kim ; Yong-Kwan Kim |
DOI |
http://dx.doi.org/10.5207/JIEIE.2012.26.5.048 |
Keywords |
Photovoltaic Power System ; Power System Quality ; Harmonic Measurement ; Harmonic Assessment ; K-Factor |
Abstract |
This paper analyzes the characteristic of gird connected photovoltaic power generation system which is available to connect the utility. Renewable energy photovoltaic power system has been linked to the system to analyze the impact of photovoltaic system. It is measured that power data for the Grid connected photovoltaic power plant with instantaneous measuring and 3-sec measuring for 7 days. Harmonic field measurements have shown that the harmonic contents of a waveform varies with time. A cumulative probability approach is the most commonly used method to solve time varying harmonics. So, it is used 50[%] cumulative probability approach. This paper provides an in depth analysis on power quality field measurement of the Grid connected photovoltaic power plant. |