Abstract This paper presents the comparison of the earth resistivity obtained from the measurements made with the three-electrode and four-electrode fall-of-potential techniques. The p-a curve obtained from Wenner four-electrode method in undisturbed earth is in good agreement with the p-1 curve obtained from the three-electrode method based on the fall-of-potential method. However, The p-a curve in disturbed earth with moisture and freezing is significantly different with the p-1 curve. The p-a curve is considerably sensitive to the freezing and the moisture present in the earth surface compared to the p-1 curve. Thus to determine the actual earth resistivity, it is necessary to take into account the earth surface conditions when measuring the earth resistivity.