Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Characteristics of the Switching Surge Voltages Induced at Metal Flexible Conduits Due to Ground Faults
Authors Bok-Hee Lee ; Gun-Jin Shin ; Hee-Yeoul Park ; Sang-Hyun Um ; You-Ha Kim
DOI http://dx.doi.org/10.5207/JIEIE.2013.27.5.074
Page pp.74-80
ISSN 1225-1135
Keywords Metal Flexible Conduit ; Switching Surge ; Ground Fault ; Nonmagnetic Conduit ; Circuit Parameter
Abstract This paper presents the transient behavior of the switching surge voltages generated by interruption of DC ground fault currents flowing through metal flexible conduits. All fault circuits consist of line parameters such as resistance, inductance, capacitance and conductance. The use of nonmagnetic metal conduits should be taken into account in order to reduce the inductance of battery charger distribution circuits. The frequency-dependent circuit parameters of metal flexible conduits were measured. The switching surge voltages generated at the ground fault circuit consisted of steel-galvanized alloy and aluminium conduits were investigated. As a result, the impedances of metal flexible conduits are significantly increased over the range of the frequency above 10 kHz and the switching surge voltages generated along aluminium flexible conduit are lower than those along steel-galvanized alloy conduit when DC fault current is interrupted.