Title |
A Study on the Ground Fault Current Distribution by Single Phase-to-Neutral Fault Tests in Power Distribution System |
Authors |
Kyung-Chul Kim ; Chang-Hun You |
DOI |
http://dx.doi.org/10.5207/JIEIE.2013.27.7.037 |
Keywords |
Phase to Neutral Fault ; Ground Fault Current Distribution ; Three-Phase Four-Wire Multigrounded Neutral Distribution System ; Artificial Fault Generator |
Abstract |
Phase to ground faults are possibly one of the maximum number of faults in power distribution system. During a ground fault the maximum fault current and neutral to ground voltage will appear at the pole nearest to the fault. Distribution lines are consisted of three phase conductors, an overhead ground wire and a multigrounded neutral line. In this paper phase to neutral faults were staged at the specified concrete pole along the distribution line and measured the ground fault current distribution in the ground fault current, three poles nearest to the fault point, overhead ground wire and neutral line. A simplified equivalent circuit model for the distribution system under case study calculated by using MATLAB gives results very close to the ground fault current distribution yielded by field tests. |