Title |
A Study on the Installation Method of Down Conductors of the Lightning Protection System, using Rebar in Reinforced Concrete Structures |
Authors |
young-Chul Lee ; Ju-Cheol Lee |
DOI |
http://dx.doi.org/10.5207/JIEIE.2013.27.7.101 |
Keywords |
Lightning Protection System ; Down-Conductor System ; Methods of Joining Reinforcing Rods |
Abstract |
IEC Standards on lightning protection system specify the use of natural components as down conductors. This paper provides an analysis of problems revealed from our field investigation and survey conducted for the relevant experts in the construction site where natural components are used as down conductors. It also considers a suitable condition for installing natural components as down conductors in accordance with the latest version of the standard. As a result, when rebars of reinforced concrete are used as down conductors, vertical bars consisting of rebars of which thickness is not less than D13(127 ㎟) should be connected by welding, clamps or bound joints, using appropriate connection components conforming to IEC Standards. The lashed joints, however, shall not be applied for down conductors. |