Analysis of On-Line Partial Discharge in Air-Coolded Gas Turbine Generator |
Authors |
Eun-Chun Lee ; Tae-Sik Kong ; Jae-Chul Kim ; Hee-Dong Kim |
DOI |
http://dx.doi.org/10.5207/JIEIE.2014.28.7.041 |
Keywords |
On-Line ; Partial Discharge ; Generator ; Stator Windings ; TGA |
Abstract |
The on-line partial discharge (PD) in stator windings of air-cooled gas turbine (GT) generator (119.2MVA, 13.8kV) is measured and analyzed in this paper. This generator was designed by global vacuum pressure impregnation (VPI). The generator failed two times at top bar (16T) of phase B in the stator slot. Six epoxy-mica capacitors were installed in three phases of GT generator. On-line PD test was performed on GT generator using turbine generator analyzer (TGA). TGA showed that the normalized quantity number (NQN) and the PD magnitude(Qm) were high in phase B. Internal discharges were generated in phases A, B and C. The trend analysis of NQN and Qm value are obtained in order to monitor the insulation condition in GT generator stator windings. Phases A and C were in good condition. But phase B had deteriorated significantly. |