Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Study on Insulation Diagnosis of Poor Contact between Electrode and Solid Insulator in Eco-Gas
Authors Dong-Young Lim ; Eun-Hyeok Choi ; Sungwoo Bae ; Sang-Tae Choi ; Kwang-Sik Lee ; Byoung-Ju Choi
DOI http://dx.doi.org/10.5207/JIEIE.2015.29.10.097
Page pp.97-103
ISSN 1225-1135
Keywords Insulation Diagnosis, Partial Discharge, Poor Contact, Radiated Electromagnetic Waves
Abstract This paper presents the characteristics of partial discharge and radiated electromagnetic waves in the existence of a poor contact for the insulation diagnosis of eco-friendly power equipment. AC surface discharge experiment was conducted to simulate the poor contact between a hive voltage electrode (anode) and a solid insulator in N2/O2 mixture gas under a non-uniform field. The partial discharge voltage to be measured at 0.3MPa increased with the increase of the poor contact gap and was saturated with the gap. In addition to the partial discharge characteristics, it was verified that the defect of the poor contact can be diagnosed using the radiated electromagnetic waves due to the partial discharge, which measured by a biconical EMC antenna and a spectrum analyzer.