Title |
A Study on the Measurement of the Winding Resistance Influences the Efficiency Evaluation of 3phase Induction Motors |
Authors |
Byung-Guk Kang ; Kwang-Min Kim ; Ju Lee |
DOI |
http://dx.doi.org/10.5207/JIEIE.2016.30.3.073 |
Keywords |
3Phase Induction Motor ; Efficiency ; Winding Resistance ; Evaluation ; Test Method |
Abstract |
3phase induction motor consumes 40% of national electric power. so It is one of the most important electric device for the national power policy. The efficiency measurement is carried out by IEC standards. After the temperature rise test, It’s difficult to measure the winding resistance immediately. because of inertia and power cut-off time. Therefore, IEC standards suggest the measurement time. But during the measurement time, the winding temperature cools down. It causes the value of winding resistance is variable. Several conditions which possibly occurred by the measurement time of IEC 60034-1 are suggested. and The efficiency evaluation of 3phase induction motors is carried out by IEC 60034-2-1 with the several conditions. As the results, we find out the winding resistance rapidly goes down within 15 sec. so It proves that the winding resistance should be measured within 15 sec. for the efficiency evaluating of 3phase induction motor. |