Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Condition Monitoring of Electric Power Systems using Fiber-Optic Temperature Sensor with Epoxy Resin
Authors Dae-Gil Kim ; Umesh Sampath ; Minho Song
DOI http://dx.doi.org/10.5207/JIEIE.2016.30.6.067
Page pp.67-73
ISSN 1225-1135
Keywords Fiber-Optic Temperature Sensor ; Fresnel Reflection ; Epoxy Resin
Abstract A novel fiber-optic sensor, which is based on Fresnel reflection measurement, is suggested for condition monitoring of electric power system. The sensor head is constructed by covering a fiber end tip with thermo-sensitive epoxy polymer resin. The different thermo-optic coefficients of optical fiber and polymer resin change the intensity of Fresnel reflections from the interface. The temperature can be calculated by monitoring the variation in the Fresnel reflection intensity. The temperature sensitivity could be improved by adjusting the ratio of the curing agent. In order to evaluate the feasibility of the sensor head, temperature measurements were performed in 45∼115 ℃ temperature range. From the experiments, the proposed sensor successfully measured and recovered the temperature information and the linear-fitted value of R2 was 0.99759.