Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Effect of the Wind Power Generation Facilities on the Power Quality of Power System
Authors Dong-Chul Kwon ; Dong-Young Yi
DOI http://dx.doi.org/10.5207/JIEIE.2016.30.9.026
Page pp.26-32
ISSN 1225-1135
Keywords Wind Power Generation ; Power Quality ; Power System
Abstract In this study, we have investigated the effect of the wind power generation facilities on the power quality of interconnected wind power generation system. When the wind power generation facility was connected to the distribution system, whether the wind power generation is under operation or not, voltage variation was increased to 0.34%, peak factor of current was increased to 0.145 and phase difference was increased to 0.6° deviation(2.5 times). Harmonic current % in orders was increased to 29.4%, 14.7% and 3.73% at 3rd, 5th and 9th orders respectively. When the wind power generation facilities were not under operation, harmonic current THD(263.7%) was above the technical criteria of domestic power company(5%) and also, harmonic current % in orders(12.4%, 14.2%, 19.4% and 8.06% at 3rd, 5th, 7th and 9th respectively) were above the technical criteria of domestic power company(below 4% under 11th orders). Therefore, it was confirmed that the wind power generation facility, when it was connected to the existing distribution system, made bad influence on the power qualities.