Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Implementation of Test Facility for DC AFCI Performance Evaluation based on UL1699B Standard
Authors Jae-Beom Ahn ; Jin-Han Lee ; Hyun-Bin Jo ; Jin Lee ; Hong-Je Ryoo
DOI http://doi.org/10.5207/JIEIE.2021.35.9.009
Page pp.9-15
ISSN 1225-1135
Keywords Arc generator; DC AFCI; PV system; Series arc; UL1699B
Abstract This paper deals with the implementation of test facility for DC AFCI(Arc fault circuit interrupter) series arc detection performance evaluation based on UL1699B standard. The implemented test facility consists of DC source, decoupling network, line impedance, inverter and arc generator. The developed electric arc generator enables precise control for spacing between the arc electrodes. Implemented test facility complies with a single full string model presented on UL1699B. Mode 1 to Mode 4 are presented as test modes. The test conditions of inverter voltage, current, minimum arc current conditions, electrode separation speed and distance are satisfied by implemented test facility when arcing occurred in all test modes. Also the series arc detection performance evaluation result of DC AFCI under the mode 1 condition is presented. The implemented test facility is expected to be applied to the series arc detection performance evaluation of DC AFCI under all test mode conditions.