Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.

  1. (Korea Electric Power Corporation (KEPCO))
  2. (KEPCO International Nuclear Graduate School, Korea)



Lightning Induced Voltage, ATP(Alternative Transient Program), Parametric Analysis

1. Introduction

Lightning strikes near a distribution line will induce voltages into the line from the electric and magnetic fields produced by the lightning stroke. These induced voltages are much less severe than direct strikes, but close strikes can induce enough voltage to flash insulation and damage poorly protected equipment. The charge and current flow through the lightning channel creates fields near the line. These fields induce voltages on the line. The vertical electric field is the major component that couples voltages into the line. As the highly charged leader approaches the ground, the electric field increases greatly; and when the leader connects, the electric field collapses very quickly. The rapidly changing vertical electric field induces a voltage on a conductor, which is proportional to the height of the conductor above ground.

Most measurements of induced voltages have been less than 300kV, so the most common guideline for eliminating problems with induced voltages is to make sure that the line insulation capability (CFO) is higher than 300kV[1]. Therefore, lines with insulation capabilities less than 300kV have many more flashovers due to induced voltages.

Fig. 1. Direct and indirect lightning strikes on distribution lines

../../Resources/kiiee/JIEIE.2019.33.3.019/fig1.png

There are methods to mitigate lightning overvoltage and its consequences, such as back-flashover. In case of back flashover, reducing ground resistance of supporting structure (i.e. tower, pole) is one way to limit excessive potential rise of supporting structures,. which cause back-flashover, by lightning current discharge to ground. In case of induced over-voltage, however, it is unclear that improving ground (ex. reducing ground resistance) is really necessary to mitigate induced over-voltage. For reader’s information, in EPRI’s handbook for lightning mitigation[1], improving ground is not a mitigation option for reducing induced over-voltage (refer Table 1). But no further specific descriptions about why improving grounding is not included in migitaion options are not given in the report.

Table 1. Typical power line lightning mitigation options[1]

../../Resources/kiiee/JIEIE.2019.33.3.019/tb1.png

In addition, as for overhead ground wires of distribution lines, a lot of KEPCO engineers has believed that the purpose of overhead ground wires is to protect lines from direct lightning. However, IEC 60071, which is an international standard of insulation coordination, states in the related sections (i.e. 6. Special considerations for overhead lines, 6.4.1 distribution lines) that "Protection by shield wires is useless because tower earthing and insulation strength cannot economically be improved to such a degree that back flashovers are avoided."[2] Therefore, the lightning performance of distribution lines, therefore, is largely determined by the ground flash density and the line height.

In this paper, a lot of numerical simulations using EMTP were conducted to understand how much ground improvement, overhead ground wires and surge arresters contribute to mitigation of lightning induced over-voltages. Firstly, compiled LIV-ATP process briefly explained and the execution times are compared with the existing LIV-ATP. And the paper also provide parametric analysis results on the induced voltage with compiled LIV-ATP, for lighting arrester and ground resistance.

2. EMTP model for LIV calculation

ATP (Alternative Transient Program) version of EMTP (Electro-Magnetic Transient Program) has been very widely used for lightning overvoltage analysis and insulation coordination under lightning strikes. Since analysis of lightning induced overvoltage requires rather rigorous electromagnetic field calculation comparing to circuit analysis, however, original ATP code could not be used for lightning induced voltage analysis. To overcome this limitation, LIV (Lightning Induced Voltage) computation model using MODELS, which is an internal programming language for ATP, has been proposed recently.

2.1 LIV-ATP

The LIV-ATP program by Høidalen is proposed and described in [2][2]. It is based on the analytical solution of the lightning-electromagnetic field equations for a lossless ground using the approach proposed in [3][3] by Rusck.

2.2 Compiled LIV-ATP

Software package MinGW32 includes appropriate tools to link of the object file generated from c language version of LIV-ATP MODELS code with ATP object file (tpbig.a). By gcc.exe, g77.exe and make.exe programs the fortran compiler will create the object file from FORTRAN ATP written in FORTRAN language and C compiler will create the object file from the relay source code written in C language.

These will be subsequently linked with other object files and libraries and compiled, which will create a new simulation ATP program in file tpbig.exe containing a LIV-ATP. The compile and link process is clearly described in Figure. 2.

Fig. 2. Linking and compiling the process of ATP in MinGW32[3]

../../Resources/kiiee/JIEIE.2019.33.3.019/fig2.png

Figure. 3(a) shows comparison of original and compiled version of LIV-ATP example, which has two conductors and 500m of line length. The point of lightning strike to ground is 100m horizontally away from the line. Figure. 3(b) shows that calculated induced voltages at both terminal is consistent.

Fig. 3. Comparison of calculation results of original and compiled LIV-ATP examples

../../Resources/kiiee/JIEIE.2019.33.3.019/fig3.png

Elapsed times for running ATPDraw models were compared and the results were shown in Figure. 4. Since two conductos are possible to be modeled in the original LIV-ATP MODELS, case-1 results were selected and compared in regards to computational elapsed time. It can be seen that computational speed is significantly improved by using compiled MODELS version of LIV-ATP.

Fig. 4. Comparison of calculation time between original & compiled LIV-ATP

../../Resources/kiiee/JIEIE.2019.33.3.019/fig4.png

3. LIV calculation in distribution lines

In this chapter, EMTP models for lightning induced voltage on 22.9kV distribution lines were described. Using the models, performances of various distribution line protection schemes under indirect lightning strikes were evaluated.

3.1 ATPDraw Models

Figure. 5 shows examples of distribution line model with various lightning protection schemes using ATPDraw, which is a public domain graphic pre-processor for ATP. The line length is assumed to be 2km and lightning strikes at the center of the line with horizontal distance of 100 meters.

Fig. 5. ATPDraw models for LIV study on 22.9kV distribution lines

../../Resources/kiiee/JIEIE.2019.33.3.019/fig5.png

The following 4 types of protection schemes were implemented to evaluate each model’s lighting protection performance.

- Case-1 : Neither overhead groundwires nor Surge arresters. Neutral wires are grounded at every 500 meters according to related KEPCO standard

- Case-2 : Overhead groundwires (No arrester)

- Case-3 : Surge arresters (No overhead groundwire)

- Case-4 : Both overhead groundwires and Surge arresters are installed

3.2 Lightning Performance Evaluation results

Figure. 6~Figure. 8 show the calculated voltage difference between phase and neutral conductor, which is a voltage along line post insulator. If this voltage difference exceeds insulator’s insulation strength, then flashover between conduct and neutral conductor will occur causing line-to-ground fault. The magnitude of lightning current is assumed to be 100kA or 20kA.

1) 20kA of lightning current magnitude : Lightning falls on ground surface horizontally distant from #20 pole, which is a center pole of 2km distribution line.

· Figure. 6(a) shows voltages along LP insulators at #20, #25, #30 and #35 poles (Case-1). The closest #20 pole from lighting strike point shows the maximum voltage of about 50kV.

· Figure. 6(b) shows the case of overhead ground wires installed (no surge arresters, Case-2). By shielding effect of overhead ground wires, the maximum insulator voltage is reduced to about 40kV.

· Figure. 6(c) shows the case of surge arresters (no overhead ground wires, Case-3). From the voltage waveforms, some surge arresters operated and insulator voltages were reduced consequently.

· Figure. 6(d) shows the case of Case-4 with overhead ground wires and surge arresters installed. From the voltage waveforms, we can see no surge arrester was operated.

Fig. 6. Differential voltage between phase and neutral conductors under different line protection conditions (20kA)

../../Resources/kiiee/JIEIE.2019.33.3.019/fig6.png

2) Figure. 7 show the cases of 40kA lightning strikes.

Fig. 7. Differential voltage between phase and neutral conductors under different line protection conditions (40kA)

../../Resources/kiiee/JIEIE.2019.33.3.019/fig7.png

3) 100kA of lightning current magnitude : Lightning falls on ground surface horizontally distant from #20 pole, which is a center pole of 2km distribution line.

· Figure. 8(a) shows voltages along LP insulators at #20, #25, #30 and #35 poles (Case-1). From the voltage waveforms, we can see the insulator voltages exceeded their insulation strength and flash overs are occurred.

· Figure. 8(b) shows the case of overhead ground wires installed (no surge arresters, Case-2). By shielding effect of overhead ground wires, there was no flashover but the maximum insulator voltage is close to 200kV, which is the maximum insulation strength under impulse current.

· Figure. 8(c) shows the case of surge arresters (no overhead ground wires, Case-3). From the voltage waveforms, some surge arresters operated and insulator voltages were greatly reduced under about 50kV, which is the knee point voltage of surge arresters.

· Figure. 8(d) shows the case of Case-4 with overhead ground wires and surge arresters installed. From the voltage waveforms, we can see surge arresters were operated and there is no big difference from the case of Case-3.

Fig. 8. Differential voltage between phase and neutral conductors under different line protection conditions (100kA)

../../Resources/kiiee/JIEIE.2019.33.3.019/fig8.png

3.3 Parametric Analysis of Lighting Induced Over voltages

In this section, overvoltages on phase and neutral conductor at the nearest pole from lightning strike point were calculated varying the pole’s ground resistance from 50Ω to 100Ω.

It can be seen from the Figure. 9 that as pole ground resistance increase, phase and neutral conductor voltage increases also. However, the voltage difference, which is voltage applied along line-post insulator, decreases as pole ground resistance increases.

Fig. 9. Pole ground resistances vs. conductor/ neutral voltages

../../Resources/kiiee/JIEIE.2019.33.3.019/fig9.png

These phenomena can be explained from the fact that neutral conductors are located closer to pole ground than phase conductors so their voltages are more sensitive to the change of resistance. This simulation results imply that reducing ground resistance does not contribute to mitigation of overvoltage along line-post insulators and problems of line post insulator flashover.

4. Conclusions

In this paper, we presented lightning induced voltage calculation technique using compiled LIV-ATP. With the presented compiled MODELS version of original LIV-ATP, its computational speed of LIV-ATP was significantly improved and parametric analysis of LIV, which requires running a lot of simulation cases, was remarkably facilitated. Based on a series of simulations using the code, evaluations of lightning protection performances of various protection schemes were conducted. The calculation results show the effectiveness of overhead ground wires and surge arresters as protection methods from insulation failures at line-post insulators.

References

1 
EPRI , 2004, Handbook for Improving Overhead Transmission Line Lightning Performance, pp. 4-8Google Search
2 
IEC 60071-2 , 1996-12, Insulation Coordination – Part 2 Applcation Guide, 3rd Edition, pp. 107Google Search
3 
Janicek Frantisek, Mucha Martin, September 22-24, 2006, Multifunctional Relay Developed in ATP FOREIGN MODEL and C++, Proceedings of the 6th WSEAS International Conference on Simulation, Modelling and Optimization, Lisbon, PortugalGoogle Search
4 
2006, T & D System Design and Construction for Enhanced Reliability and Power Qualit, EPRI Technical ReportGoogle Search
5 
Høidalen Hans Kr., 2003, Calculation of Lightning-induced Voltages in MODELS Including Lossy Ground Effects, in IPSTGoogle Search
6 
Rusck S., 1958, Induced lightning over-voltages on power transmission lines with special reference to the over-voltage protection of low-voltage networks, in Transactions of the Royal Institute of Technology. No. 120, Stockholm, SwedenGoogle Search
7 
Silva J. P., Araújo A. A., Paulino J. S., Dommel H. W., 2001, Calculation of Lightning-Induced Voltages with RUSCK’s Method in EMTP, in IPSTDOI
8 
Paolone M., Perez E., Borghetti A., Nucci C. A., Rachidi F., Torres H., 2005, Comparison of Two Computational Programs for the Calculation of Lightning-Induced Voltages on Distribution Systems, in IPSTGoogle Search

Biography

Dong-Hyuk Ha
../../Resources/kiiee/JIEIE.2019.33.3.019/au1.png

He received B.S and M.S degree in electrical engineering from Kwang -Woon and ChonNam university in 1979 and 2019 respectively.

He has joined Korea Electric Power Corporation since 1987.

Jong-Kee Choi
../../Resources/kiiee/JIEIE.2019.33.3.019/au2.png

He received B.S degree in electrical engineering and M.S/Ph.D in power system engineering from Dong-guk and Hong-ik university in 1993, 1995 and 2007 respectively.

He joined Korea Electric Power Corporation in 1995 and is a principal researcher, in which interested power system grounding analysis, at present.

Yong-Beum Yoon
../../Resources/kiiee/JIEIE.2019.33.3.019/au3.png

He received B.S degree in electrical engineering and M.S/Ph.D in power system engineering from Pusan National Univ. and Seoul National Univ. in 1984, 1986 and 1995 respectively.

He joined Korea Electric Power Corporation in 1986 and was a head of transmission and substation research laboratory.

He is currently with the Department of Energy Policy and Engineering, KEPCO International Nuclear Graduate School.

His current teaching and research interests include electric power economics and microgrid.