(Jun Oh Kim)
1iD
(Sun Kyu Choi)
2iD
(Seung Wan Kim)
†iD
-
(Student, Dept. of Electrical Engineering, Chungnam National University, Korea)
-
(Senior Researcher, Convergence Technology Lab., KEPCO Research Institute, Korea)
Copyright © The Korean Institute of Illuminating and Electrical Engineers(KIIEE)
Key words
Indirect Lightning, Low voltage, Medium voltage, Pole transformer, Surge arresters
1. Introduction
For a distribution network protection from lightning, several combinations from surge
arresters (SAs), overhead ground wires (OHGWs), and grounding system can be used.
In case of Korea Electric Power Company (KEPCO), a distribution network utility of
South Korea, all of them have been used with multi-grounded system until 2021. However,
it has always been debatable whether installing all of the equipment or not since
there is a trade-off issue between an economic efficiency and an acceptable lightning
performance by utilities.
A lightning performance evaluation has been studied in many literatures. Reference
[1] carried out a study to test how the presence of the buildings nearby the overhead
lines influences the lightning performance of the lines. The authors focused on the
lightning electromagnetic pulse (LEMP) attenuation of indirect strokes provided by
the buildings to evaluate the lightning performance. The results show that the LEMP
effect provided by the buildings significantly improves the lightning performance,
therefore, the LEMP reduction effect must be considered to calculate the lightning
performance accurately. However, the lightning performance is evaluated for a single
conductor with a 150kV withstand voltage. Therefore, it is not possible to estimate
the lightning performance reflected the LEMP effect for multi-conductor lines with
lateral.
Reference [2] suggested the stratified sampling technique application to the assessment of the
indirect lightning performance of low voltage (LV) distribution lines. They experiment
three different neutral grounding configurations to analyze the effect of the neutral
grounding of the line against the indirect lightning. The results show that neutral
grounding improves the LV line performance whereas additional neutral grounding appears
to worsen the induced voltage stress at the customers' connection point. However,
the line is composed of four unshielded insulated wires except for the overhead ground
wire.
Reference [3] proposed the recursive stratified sampling technique to reduce the computational
time for the lightning performance of the distribution. The Standard Monte Carlo (MC)
and Stratified Sampling methods are compared, and the results show that the proposed
procedure has the advantages of not only reducing computational time but also reducing
the importance of the choice of the smallest area including the perspective stroke
locations of the events. However, the proposed procedure is considered according to
the SAs installation interval for a single overhead line and network composed by a
main feeder, and laterals without SAs.
Reference [4] addressed the influence of reflecting on actual insulation volt-time curves and suggested
reducing the threshold level – 1.2 times critical flash over voltage (1.2CFO) in the
paper – to estimate a more realistic flashover rate of distribution lines. They conduct
the different flashover criteria of multiply factors 1.5 and 1.2, respectively. The
results show that the threshold level of the simplified 1.5CFO criterion traditionally
used is capable to underestimate the flashover rate of the line due to indirect stroke.
However, the results did not reflect the realistic conditions of the distribution
network including the equipment such as the shielding wires and SAs.
Reference [5] calculated the flashover rate due to direct negative lightning and considered the
6.6kV distribution lines with SAs and OHGW installing intervals. The flashover rate
of distribution line is calculated for the negative first strokes and negative subsequent
stroke. However, the ground resistance of SA and OHGW is used as a fixed value. Therefore,
the effect of the grounding resistance on the flashover rate cannot be confirmed.
In addition, the LV line was modeled except for the transformer model.
Reference [6] proposed the analytical approach to reduce the required computer resources significantly
and investigated the influences of the shield wires in lightning performance. The
simulation is reflected in a vertical line and horizontal line configurations by adding
multiple shield wires. The results show that adding multiple shield wires can improve
the lightning performance. However, it is limited in deriving a realistic operation
plan for insulation coordination between devices because it does not reflect the devices
such as insulators, SAs, and transformers.
Reference [7] investigated indirect lightning flashover rate considering first and subsequent strokes.
Furthermore, analysis of the parameters affecting the flashover rate, such as front-time
value of the current, soil resistivity, stroke velocity, is also performed. However,
a simplified line model is considered to calculate the lightning performance: a single
overhead line from the Cigré model, 2km long, 10m high.
Reference [8] proposed a statistical method to estimate the lightning performance associated with
the lightning interception probability distribution of the line conductors not using
the MC method traditionally used in the relevant studies. In addition, they analyze
the effects of the line parameters, shielding of nearby objects, soil resistivity,
and the lightning crest current distribution on the lightning performance of distribution
lines quantitatively. However, the simplified coupling model of IEEE std. 1410 and
statistical lightning attachment model are implemented to assess and expected the
lightning performance.
In this paper, to overcome the limitations of the previous works, we focus on the
consideration of both MV and LV lines for lightning performance evaluation of KEPCO
distribution lines and the analysis of the sensitivity of the lightning performance
of the distribution lines to different configuration of LV and MV grounding systems,
distance between SAs, as well as presence of OHGWs.
The rest of the paper is structured as follows. Section 2 thoroughly describes the
models adopted in the study. Section 3 presents the time domain simulations for indirect
lightning events with an analysis of the influence of the grounding resistance and
the presence of medium voltage/low voltage (MV/LV) transformers and lines. Section
4 presents the calculation of the lightning performance of the LV lines. Section 5
outlines the conclusion.
2.Models of MV/LV Distribution Lines and Components
This section describes the geometrical configuration of the line and all the components
adopted in the EMTP simulations.
2.1 Model of the Pole
3-phase MV lines with rated voltage of 22.9kV line to line (13.2kV line to ground)
is considered. The phase conductors are at 13m height from the ground. An OHGW and
a neutral conductor are at 14.6m and 11.8m, respectively, above from the ground. Diameters
of the phase conductors are 1.615 and those of the neutral conductor and OHGW are
0.95cm. We considered 5 conductors (OHGW, 3-phase conductors, and neutral wire) as
conductor 1 to 5. The horizontal distance of each conductor y1 to y5 are 0m, –0.5m,
0.5m, 1.0m, and 0m, respectively. The distance between poles is 50m.
2.2 Grounding Models
The pole consists of two sections in our model. One is between the OHGW and the neutral
point and the other is between the neutral point and ground. They have 2.8m and 11.8m
lengths, respectively. To reduce the computational burden of the simulation, all the
lengths are rounded up to 5m unit. So, both sections have 5m and 10m, respectively,
in our model. The EMTP model still worked well with this approximation without causing
any significant error.
The value of surge impedance on concrete pole is assumed equal for both the sections,
namely, $Z_{p1}= Z_{p2}= 200\omega$. This value is in agreement with the experimental
data presented in [9].
The grounding effect is modeled by using Weck’s formula [10] to quantify the soil ionization. The relationship between the direct current grounding
resistance in absence of soil ionization $R_{g}$ and the grounding resistance considering
soil ionization $R_{w}$ is expressed as:
where
$I$ is the current in grounding and $E_{0}$ is breakdown gradient, which is equal
to 400kV/m.
2.3 Surge Arresters and Surge Protective Devices
The current-voltage characteristic of the MV SA is shown in Fig. 1.
Fig. 1. MV SAs characteristic
According to the characteristic the SA has a nominal discharge current of 10kA corresponding
to a lightning impulse protection level equal to 64.2kV. The SA can be therefore considered
of distribution class with high duty. The reference voltage corresponding to 1mA is
equal to 39.8kV that correspond to a RMS voltage equal to 28.2kV, that is larger than
the system rated voltage of 22.9kV, and is consistent with a MV distribution system
with resonant or insulated neutral.
By comparison with technical data of SAs of rated voltage 21kV with similar residual
voltages at 8/20μs discharge currents, the residual voltage at 10kA steep front discharge
current is of about 71kA. This value, together allow to estimate the dynamic response
of the SA by using the model proposed by [11].
2.4 Distribution Transformer Model
We used a black box transformer model inferred by using admittance matrices at logarithmically
spaced frequencies between 1kHz and 1MHz measured on a distribution transformer. The
transformer has rated power 100kVA, rated voltages 15/0.4kV and is an oil insulated
pole mounted.
The admittances of the transformer were measured by a virtual instrument composed
by an oscilloscope and a signal generator driven by a Labview environment. The measurement
and identification procedure are the same presented in [12].
The transformer has 3MV terminals and 4LV terminals. So, the transformer has 7 terminals
plus the tank ground terminal. The neutral is assumed grounded. The admittance matrices
have therefore order 6. In particular, denoting the MV terminals by the symbols 1,
2, 3, and the LV terminals by 4, 5, 6, the transformer admittance matrices, one for
each frequency can be expressed as:
where each element has the following relationships:
The frequency responses were fitted by rational functions by using a Vector Fitting
tool [13] and an enforcing passivity procedure that implements the method proposed in [14]. The fitted rational functions are used to define the admittances of the multi-port
equivalent network of the transformer by means of the following relationship:
The multi terminal π-equivalent circuit can be implemented in EMTP-like programs by
means of frequency dependent equivalent networks, i.e. equivalent circuits with lumped
parameters such as resistances, inductances and capacitances whose frequency response
match the fitted admittances of the multi-port network, schematically shown in Fig. 2.
Fig. 2. Generic structure of a FDB (Frequency Dependent Branch) in EMTP
The procedure for the selection of the parameters of the equivalent network is the
same illustrated in [15].
3.Overvoltages in MV and LV Lines Due to Indirect Lightnings
3.1 Transferred Overvoltages Due to Indirect Lightnings
In this subsection, the overvoltages transferred to the secondary side of the distribution
transformer and the response of the line are presented. An external electromagnetic
field originated by a lightning return stroke in the vicinity of the line is considered.
Fig. 3 shows the topology of the line and a lightning stroke location. The red circles indicate
the poles grounded with $R_{ga}$= 25Ω and all the other poles are grounded with $R_{gb}$=
300Ω. The line length is 2000m. The line terminations are connected to the matrix
of the line surge impedances. 40 poles are considered. The stroke location is at 50m
away from the center of the line and equidistant to the line terminations.
Fig. 3. Top view of the line and the strike location (X) for the first simulation
case
It is assumed that the return stroke velocity is 1.5×108m/s and the Transmission Line
(TL) model is adopted for the return stroke. The channel-base current is assumed to
has a 12kA peak amplitude and a maximum time derivative of 40kA/μs, which are the
medians of subsequent return strokes [16] and are represented as:
where
Equations (7) and (8) have the following parameters [17]:
$I_{01}=10.7$ kA, $\tau_{11}=0.25\mu s$, $\tau_{21}=2.5\mu s$, $n_{1}=2$,
$I_{02}=6.5$ kA, $\tau_{12}=2.1\mu s$, $\tau_{22}=230\mu s$, $n_{2}=2$.
The electromagnetic field is calculated by using the model described in [18].
In the following figures, both the total voltages and the voltages across the insulators
are reported. The former is the voltages respect to the remote far ground assumed
as undisturbed, the latter is the voltages across the MV insulators. The insulator
voltages are equal to the voltage between the MV phase conductors and the steel arm
of the pole, due to the presence of the grounding lead, there is a little difference
between the voltage of the OHGW (or shield wire) and the neutral, therefore the insulator
voltage has been taken equal to the voltage between the MV phase wires and the neutral
wire. The ground resistivity of the ground σg is 1mS/m and the relative permittivity
$\epsilon_{rg}$ is equal to 10.
Fig. 4 shows the overvoltages on the MV side due to a subsequent stroke, while Fig. 5 shows the voltages transferred on the LV-side of the transformer. The neutral voltage
is the same in both figures. In Fig. 5(a), the overvoltages are calculated with respect to the voltage of the neutral conductor.
The same comparison is provided in Fig. 6 and Fig. 7 for the case of a first return stroke. In all the cases, the grounding resistance
$R_{ga}$ is set to 25Ω.
Fig. 4. Overvoltages on the MV side due to a subsequent stroke. $\sigma_{g}=1$mS/m,
$\epsilon_{rg}=10$
Fig. 5. Overvoltages on the LV side due to a subsequent stroke. (a) total voltage,
(b) phase-to-neutral. $\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$
Fig. 6. Overvoltages on the MV side due to a first stroke. $\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$
Fig. 7. Overvoltages on the LV side due to a first stroke. (a) total voltage, (b)
phase-to-neutral. $\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$
3.2 A Case of MV and LV Lines on the Same Poles
The presence of the LV conductors does not affect the overvoltages induced on the
MV line. On the other hand, in order to calculate the accurate response of the LV
line to an external electromagnetic field, it is necessary to consider both the MV
and LV wires in the same lightning-induced overvoltage-line model.
Fig. 8 shows the topology of the considered double circuit line and the stroke location.
The poles in which Rga is varied are indicated in red. The simulations are repeated
in case MVSAs are installed at the poles indicated by the blue circles.
Fig. 9 shows the overvoltage induced by a first stroke at 50m from the line center, as represented
in Fig. 8. Fig. 10 shows the same overvoltages but referred to the neutral voltage, it is the same as
in Fig. 6 since the LV phase conductors do not affect the overvoltages in the MV ones and the
neutral.
In this case, very dangerous overvoltages arise in the LV conductors, which could
also result in flashovers of the cable insulation. The presence of SAs on the MV line
is only partially effective in reducing the overvoltages on the LV conductors, as
the peak reduces from 25kV to slightly less than 15kV.
Fig. 8. Top view of the line and the strike location (X) for the second simulation
case
Fig. 9. Overvoltages on the LV conductors due to a first stroke. $\sigma_{g}=1$mS/m,
$\epsilon_{rg}=10$, $R_{ga}$=25Ω. (a) without MV SAs installed, (b) with MV SAs installed
Fig. 10. Phase-to-neutral overvoltages on the LV conductors due to a first stroke.
$\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$, $R_{ga}$= 25Ω. (a) without MV SAs installed,
(b) with MV SAs installed
3.2.1 Effect of the Grounding Resistance of the Poles
Fig. 11 shows the overvoltages peaks on the LV line induced by a first stroke for different
values of Rga. Also in this case, lowering the grounding resistance has a beneficial
effect on the total overvoltages, as it lowers the voltage of the neutral conductor,
but is not effective in reducing the phase-to-neutral voltages, which instead increase
as the value of Rga decreases. The comparison is repeated in Fig. 12 for the case in which MV SAs are installed.
Fig. 11. Overvoltages peaks on the LV line induced by a first stroke for different
values of $R_{ga}$. $\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$ without MV SAs installed
Fig. 12. Overvoltages peaks on the LV line induced by a first stroke for different
values of $R_{ga}$. $\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$ with MV SAs installed
3.2.2 Effect of the Transformer on the LV over voltages
Fig. 13 and Fig. 14 show the same comparisons of Fig. 9 and Fig. 10 in which no transformer was considered. With respect to the previous case the phase
to ground overvoltage peaks are lower, while the neutral voltage is practically unchanged.
Fig. 13. Overvoltages on the LV conductors due to a first stroke with pole transformer.
$\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$, $R_{ga}$= 25Ω. (a) without MV SAs installed,
(b) with MV SAs installed
Fig. 14. Phase-to-neutral overvoltages on the LV conductors due to a first stroke
with pole transformer. $\sigma_{g}=1$mS/m, $\epsilon_{rg}=10$, $R_{ga}$= 25Ω. (a)
without MV SAs installed, (b) with MV SAs installed
4.Indirect Lightning Performance of LV Lines
The lightning performance evaluation is conducted through the MC method, as presented
in [19-20]. Generally (e.g. [21]), the lightning performance is evaluated by drawing of a curve providing the expected
annual number of lightning events $F_{p}$ that cause voltages larger than the insulation
voltage on abscissa:
where $n$ is the number of events causing voltages higher than the insulation level,
$A$ is the area of striking and $N_{g}$ is the annual ground flash density (which
is assumed equal to 1flash/km$^{2}$/yr).
In the following simulations, 64,000 MC events (63,654 indirect events, 346 direct
events) are considered. The bounds of area $A$ are 4km far from the lines. The topology
of the considered MV and LV lines is shown in Fig. 15. MV SAs are placed every 500m, in correspondence of every pole grounded with $R_{ga}$.
Fig. 15. Topology of the MV+LV network and location of the groundings and SAs
In this Section, in order to assess the influence of different value of the grounding
resistance and of the ground conductivity, the following Cases are considered:
1. $R_{ga}$ = 25Ω, LV-line A grounded at 250m and 500m with $R_{ga}$, $R_{gn}$
= 25Ω, $\sigma_{g}=1$mS/m.
2. $R_{ga}$ = 10Ω, LV-line A grounded at 250m and 500m with $R_{ga}$, $R_{gn}$
= 10Ω, $\sigma_{g}=10$mS/m.
3. $R_{ga}$ = 10Ω, LV-line A grounded only at 500m with $R_{ga}$, $R_{gn}$ =
10Ω, $\sigma_{g}=10$mS/m.
Fig. 16 shows the indirect lightning performance of the LV line evaluated at the following
observation points:
– transformer LV terminals
– the line center
– the LV-line terminals
Fig. 16. Case 1. (a) total voltages (b) phase-to-neutral voltages
The calculation results are obtained by using (9) and refer to the total voltages (phase respect to the far ground) and the phase-to-neutral
voltages for the configuration of Case 1.
Fig. 17 reports the same results but for Case 2. By comparing the results of Case 2 respect
to those of Case 1, it can be observed that the lightning performance is significantly
improved by the higher value of the ground conductivity and the lower value of the
grounding resistances in the configuration of Case 2.
Fig. 18 refers to the configuration of Case 3, in which the neutral conductor is grounded
only at the line end. In this configuration, the performance at the line center, calculated
by making reference to the total voltages, is worse than that calculated at the line
termination. The lightning performance calculated at the termination is not meaningfully
influenced by the presence of the grounding at the mid-point of the line.
Fig. 17. Case 2. (a) Total voltages (b) Phase-to-neutral voltages
Fig. 18. Case 3. (a) total voltages (b) phase-to-neutral voltages
5. Conclusion
In this paper, the focus was on the definition of the main calculation models for
the assessment of the lightning performance of the LV distribution lines, also on
the indirect lightning performance with different configurations of lighting protection
equipment.
In the simulations, we considered at least two groundings of the LV neutral: at the
transformer and at the termination of the line. The case of a single grounding of
the neutral is not considered because it worsens too much the indirect lightning performance.
Many distribution system operators adopting TN distribution for the grounding system
type, all the more reason, have multiple grounding also for safety reasons.
From the simulation results, it can be observed that the presence of SAs on the MV
line is only partially effective in reducing the overvoltages on the LV conductors.
And obviously, the lightning performance is significantly improved by the higher value
of the ground conductivity and the lower value of the grounding resistances. It is
noteworthy that the LV line lightning performance calculated at the termination is
not meaningfully influenced by the presence of the grounding at the mid-point of the
line.
References
Tossani F., et al. , 2018, Lightning Performance of Overhead Power Distribution Lines
in Urban Areas, IEEE Trans. Power Deliv., Vol. 33, No. 2, pp. 581-588
Napolitano F., et al. , 2018, Statistical Assessment of Lightning-Induced Over voltages
in Low Voltage Lines, EEEIC / I&CPS Europe
Napolitano F., Tossani F., Borghetti A., Nucci C. A., 2018, Lightning Performance
Assessment of Power Distribution Lines by Means of Stratified Sampling Monte Carlo
Method, IEEE Trans. Power Deliv., Vol. 33, No. 5, pp. 2571-2577
De Conti A., et al. , 2010, Calculation of Lightning-Induced Voltages on Overhead
Distribution Lines Including Insulation Breakdown, IEEE Trans. Power Deliv., Vol.
25, No. 4, pp. 3078-3084
Michishita K., Hongo Y., 2012, Flashover Rate of 6.6-kV Distribution Line Due to Direct
Negative Lightning Return Strokes, IEEE Trans. Power Deliv., Vol. 27, No. 4, pp. 2203-2210
Andreotti A., et al. , 2021, An Analytical Approach to Assess the Influence of Shield
Wires in Improving the Lightning Performance Due to Indirect Strokes, IEEE Trans.
Power Deliv., Vol. 36, No. 3, pp. 1491-1498
Paulino J. O. S., et al. , 2015, Assessment and Analysis of Indirect Lightning Performance
of Overhead Lines, Electric Power Systems Research, Vol. 118, pp. 55-61
Mikropoulos P. N., Tsovilis T. E., 2013, Statistical Method for the Evaluation of
the Lightning Performance of Overhead Distribution Lines, IEEE Trans. Dielectr. Electr.
Insul., Vol. 20, No. 1, pp. 202-211
Nakada K., Sugimoto H., Yokoyama S., 2003, Experimental Facility for Investigation
of Lightning Performance of Distribution Lines, IEEE Trans. Power Deliv., Vol. 18,
No. 1, pp. 253-257
Cigr Working Group 33.01 , 1991, Guide to Procedures for Estimating the Lightning
Performance of Transmission Lines (TB 63), CIGRE
Pinceti P., Giannettoni M., 1999, A Simplified Model for Zinc Oxide Surge Arresters,
IEEE Trans. Power Deliv., Vol. 14, No. 2, pp. 393-398
Borghetti A., et al. , 2009, Lightning-induced Overvoltages Transferred Through Distribution
Power Transformers, IEEE Trans. Power Deliv., Vol. 24, No. 1, pp. 360-372
Gustavsen B., Semlyen A., 1999, Rational Approximation of Frequency Domain Responses
by Vector Fitting, IEEE Trans. Power Deliv., Vol. 14, No. 3, pp. 1052-1059
Gustavsen B., Semlyen A., 2001., Enforcing Passivity for Admittance Matrices Approximated
by Rational Functions, IEEE Trans. Power Syst., Vol. 16, No. 4, pp. 955
Gustavsen B., 2002., Computer Code for Rational Approximation of Frequency Dependent
Admittance Matrices, IEEE Power Eng. Rev., Vol. 22, No. 6, pp. 64
Berger K., Anderson R. B., Kroninger H., 1975, Parameters of Lightning Flashes, Electra,
Vol. 41, pp. 23-37
Nucci C. A., Rachidi F., Michel M. V., Mazzetti C., 1993, Lightning-Induced Voltages
on Overhead Lines, IEEE Trans. Electromagn. Compat., Vol. 35, No. 1, pp. 75-86
Napolitano F., 2011, An Analytical Formulation of the Electromagnetic Field Generated
by Lightning Return Strokes, IEEE Trans. Electromagn. Compat., Vol. 53, No. 1, pp.
108-113
Borghetti A., Nucci C. A., Paolone M., 2007, An Improved Procedure for the Assessment
of Overhead Line Indirect Lightning Performance and Its Comparison with the IEEE Std.
1410 Method, IEEE Trans. Power Deliv., Vol. 22, No. 1, pp. 684-692
Borghetti A., Nucci C. A., Paolone M., 2009, Indirect-lightning Performance of Overhead
Distribution Networks with Complex Topology, IEEE Trans. Power Deliv., Vol. 24, No.
4, pp. 2206-2213
IEEE Std 1410-2010 , 2011, IEEE Guide for Improving the Lightning Performance of Electric
Power Overhead Distribution Lines, IEEE Std 1410-2010 (Revision IEEE Std 1410-2004),
pp. 1-73
Biography
He received the B.S. and M.S. degrees in Electrical Engineering from Korea University,
Seoul, Korea, in 1988 and 1991, respectively. He is working as the head of Safety
& Health Dept. of KEPCO. He joined KEPCO in 1991 and has worked in the power distribution
field. He has work careers in head office, site, and KEPCO Research Institute.
He received the B.S. and M.S. degrees in Electrical Engineering from Korea University,
Seoul, Korea, in 2000 and 2002, respectively. He received a Ph.D. in Electrical Engineering
from HongIk University, Seoul, Korea, in 2019.
He has been with KEPRI, KEPCO, as a member of the researcher since 2003. His special
fields of interest are a grounding method, lightning, power quality and equipment
development of distribution system. Currently, he is a team manager of Disaster prediction
and Industrial safety R&D in KEPRI.
He received the B.S. and Ph.D. degrees in Electrical Engineering from Seoul National
University, Seoul, Korea, in 2012, and 2018, respectively. He has been an Assistant
Professor, Dept. of Electrical Engineering, Chungnam National University, Daejeon,
Korea, since 2018.