Title |
Development of DC Circuit Breaker using Magnet Arc Extinguisher |
Authors |
Sung-Min Lee ; Hyo-Sung Kim |
DOI |
10.6113/TKPE/2012.17.1.21 |
Keywords |
DC circuit breaker; Magnet arc extinguisher; AC distribution; DC distribution |
Abstract |
In recent years, DC distribution systems are becoming hot issue due to the increase in digital loads and DC generation systems according to the expansion of renewable energy technologies.[1,2] However, removing the fault current in DC grids is comparably difficult since the current in DC grids has no zero-crossing point like in AC grids.[3] Thus, developing dedicated DC circuit breakers for DC grids is necessary to get safety for people and electrical facilities.[4] This paper proposes magnet arc extinguishing method to develop a 300[VDC]/10[A] DC circuit breaker. The performance of the proposed DC circuit breaker was verified by an experimental circuit breaker test system built in this research. |